| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| ARC QUENCHING METHOD | AIR |
| BODY HEIGHT | 3.875 INCHES NOMINAL |
| BODY LENGTH | 6.500 INCHES NOMINAL |
| BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| BODY WIDTH | 4.125 INCHES NOMINAL |
| BOSS HEIGHT | 0.188 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.938 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.344 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 3.688 INCHES NOMINAL |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.827 INCHES NOMINAL |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | SHOCK RESISTANT AND VIBRATION RESISTANT |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES AC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 7500.0 AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE(S) |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC ALL LOCATIONS |
| POLE QUANTITY | 3 |
| RESET METHOD | MANUAL |
| SPECIAL FEATURES | CIRCUIT BREAKER SUPPLIED WITH TWO THREADED METAL INSERTS |
| SPECIAL HANDLING FEATURE | MAGNETIC |
| SPECIFICATION/STANDARD DATA | 81349-MIL-C-17361/4 GOVERNMENT SPECIFICATION |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| TERMINAL TYPE AND QUANTITY | 6 QUICK DISCONNECT, MALE |
| TEST DATA DOCUMENT | 81349-MIL-C-17361 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 5.000 MINIMUM AT 200 PCT AND 15.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| TRIP RELEASE AMBIENT TEMP RATING | 50.0 CELSIUS NOMINAL ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
| UNTHREADED MOUNTING HOLE DIAMETER | 0.190 INCHES NOMINAL |