| ACTUATOR FUNCTION | RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| BODY LENGTH | 1.531 INCHES NOMINAL |
| BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| BODY WIDTH | 1.250 INCHES NOMINAL |
| BUSHING LENGTH | 0.340 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.625 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.875 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | HERMETICALLY SEALED |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 50.0 DC ALL LOCATIONS |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 10.0 AMPERES DC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 500.0 DC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING WITH PANEL SEAL |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.855 INCHES NOMINAL |
| NOMINAL THREAD SIZE | 0.375 INCHES |
| POLE QUANTITY | 2 |
| REFERENCE NUMBER DIFFERENTIATING CHARACTERISTICS | AS DIFFERENTIATED BY SPECIAL TEST FEATURES |
| RESET METHOD | MANUAL |
| SPECIAL TEST FEATURES | NAVORD OD36190 |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.580 MINIMUM AT 200 PCT AND 6.000 MAXIMUM AT 200 PCT AND 0.080 MINIMUM AT 300 PCT AND 1.600 MAXIMUM AT 300 PCT AND 0.010 MINIMUM AT 400 PCT AND 0.630 MAXIMUM AT 400 PCT ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| ULTIMATE TRIP TIME PER POLE IN SECONDS | 2.400 MINIMUM AND 42.000 MAXIMUM ALL LOCATIONS |
| TERMINAL TYPE AND QUANTITY | 4 WIRE HOOK |
| THREAD SERIES DESIGNATOR | UNEF |
| THREAD QUANTITY PER INCH | 32 |