| POLE QUANTITY | 3 |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 150.0 AMPERES AC ALL LOCATIONS |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC ALL LOCATIONS |
| FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| TRIP RELEASE METHOD | THERMAL ALL LOCATIONS |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 100.000 MINIMUM AT 200 PCT AND |
| 300.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
| ULTIMATE TRIP TIME PER POLE IN SECONDS | 3600.000 NOMINAL ALL LOCATIONS |
| BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
| OVERALL LENGTH | 4.500 INCHES NOMINAL |
| OVERALL HEIGHT | 4.500 INCHES NOMINAL |
| OVERALL WIDTH | 8.250 INCHES NOMINAL |
| MOUNTING FACILITY TYPE AND QUANTITY | 3 UNTHREADED HOLE |
| UNTHREADED MOUNTING HOLE DIAMETER | 0.375 INCHES NOMINAL |
| TERMINAL TYPE AND QUANTITY | 6 SCREW |
| FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
| ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | 625.0 TO 1300.0 AC ALL LOCATIONS |
| THE MANUFACTURERS DATA | |
| MANUFACTURERS CODE | 89946 |
| DESIGN CONTROL REFERENCE | 457D446G20 |