| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| BODY HEIGHT | 3.180 INCHES NOMINAL |
| BODY LENGTH | 3.000 INCHES NOMINAL |
| BODY STYLE | SINGLE POLE TYPE |
| BODY WIDTH | 0.730 INCHES NOMINAL |
| BOSS HEIGHT | 0.160 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC SINGLE LOCATION |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC SINGLE LOCATION |
| MOUNTING FACILITY TYPE AND QUANTITY | 2 TERMINAL |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC SINGLE LOCATION |
| POLE QUANTITY | 1 |
| RESET METHOD | MANUAL |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| TERMINAL TYPE AND QUANTITY | 1 CLIP AND 1 COMPRESSION |
| TRIP RELEASE AMBIENT TEMP RATING | 25.0 CELSIUS NOMINAL SINGLE LOCATION |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY SINGLE LOCATION |
| TRIP RELEASE METHOD | THERMAL-MAGNETIC SINGLE LOCATION |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 15.000 NOMINAL AT 200 PCT AND 5.000 NOMINAL AT 300 PCT SINGLE LOCATION |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |