1680-00-700-7290 SUPPORT,FIRE SENSIN Index 6220-00-700-7294 RING,RETAINER

National Stock Number:
5925-00-700-7291

Federal Supply Class:
5925

National Item Identification Number:
007007291

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
3XAM1774193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
3XAM17-1.574193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
7733650P224446GENERAL ELECTRIC COMPANY
40051177948SINGER CO THE
7733650P299971LOCKHEED MARTIN CORP NAVAL ELECTRONICS & SURVEILLANCE SYSTEMS


Techincal Specification:
POLE QUANTITY3
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE1.15 AMPERES AC FIRST LOCATION
3.5 AMPERES AC SECOND LOCATION
1.15 AMPERES AC THIRD LOCATION
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
TERMINAL TYPE AND QUANTITY6 TAB W/SCREW
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS120.0 AC AND
30.0 DC ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
RESET METHODMANUAL
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
MOUNTING FACILITY TYPE AND QUANTITY6 THREADED HOLE
CASE MATERIALPLASTIC
UNPACKAGED UNIT WEIGHT13.000 OUNCES NOMINAL
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS
FREQUENCY IN HERTZ400.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS5000.0 AC AND
5000.0 DC ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT3.000 MINIMUM AT 200 PCT AND
40.000 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BUSHING LENGTH0.125 INCHES NOMINAL
BODY LENGTH2.510 INCHES MAXIMUM
BODY WIDTH2.260 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.188 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.750 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH1.812 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.750 INCHES NOMINAL
MOUNTING SURFACE TO TERMINAL END DISTANCE2.010 INCHES MAXIMUM
THREAD SERIES DESIGNATORUNC
NOMINAL THREAD SIZE0.138 INCHES
THREAD QUANTITY PER INCH32
MANUAL ACTUATOR TYPE AND QUANTITY3 TOGGLE
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDVIBRATION RESISTANT AND
SHOCK RESISTANT AND
SALT SPRAY PROOF AND
FUNGUS PROOF
ARC QUENCHING METHODMAGNETIC BLOWOUT
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SPECIAL HANDLING FEATUREMAGNETIC
FRAGILITY FACTORMODERATELY RUGGED