| ACTUATOR FUNCTION | TRIP W/SEPARATE RESET |
| ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | +800.0 TO 1600.0 DC ALL LOCATIONS |
| AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 CONTROL |
| BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 PUSH-PULL AND 1 ROTARY |
| OVERALL LENGTH | 25.000 INCHES NOMINAL |
| OVERALL WIDTH | 24.000 INCHES NOMINAL |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 800.0 AMPERES DC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 60000.0 DC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 8 THREADED HOLE(S) |
| NOMINAL THREAD SIZE | 0.375 INCHES |
| NONDEFINITIVE SPEC/STD DATA | ACB TYPE |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 DC ALL LOCATIONS |
| OVERALL HEIGHT | 24.125 INCHES NOMINAL |
| POLE QUANTITY | 2 |
| REFERENCE NUMBER DIFFERENTIATING CHARACTERISTICS | AS DIFFERENTIATED BY POLE QUANTITY,MAXIMUM CONTINUOUS LOADCURRENT RATING PER POLE,TRIPPING TIME IN SECONDS |
| RESET METHOD | MANUAL |
| TERMINAL TYPE AND QUANTITY | 4 BUS BAR |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |