| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| BODY HEIGHT | 2.327 INCHES MINIMUM AND 2.327 INCHES MINIMUM AND 2.515 INCHES MAXIMUM2.515 INCHES MAXIMUM |
| BODY LENGTH | 3.735 INCHES MINIMUM AND 3.735 INCHES MINIMUM AND 3.765 INCHES MAXIMUM3.765 INCHES MAXIMUM |
| BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPEMULTIPOLE-MULTIPLE ACTUATOR TYPE |
| BODY WIDTH | 2.985 INCHES MINIMUM AND 2.985 INCHES MINIMUM AND 3.015 INCHES MAXIMUM3.015 INCHES MAXIMUM |
| BOSS HEIGHT | 0.173 INCHES MINIMUM AND 0.173 INCHES MINIMUM AND 0.203 INCHES MAXIMUM0.203 INCHES MAXIMUM |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.985 INCHES MINIMUM AND 0.985 INCHES MINIMUM AND 1.015 INCHES MAXIMUM1.015 INCHES MAXIMUM |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
| FRAGILITY FACTOR | MODERATELY RUGGEDMODERATELY RUGGED |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS PROOF |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 40.0 AMPERES AC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 3 UNTHREADED HOLE(S)3 UNTHREADED HOLE(S) |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
| POLE QUANTITY | 33 |
| RESET METHOD | MANUAL |
| SPECIAL HANDLING FEATURE | MAGNETICMAGNETIC |
| UNTHREADED MOUNTING HOLE DIAMETER | 0.219 INCHES NOMINAL0.219 INCHES NOMINAL |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSEGENERAL PURPOSE WAREHOUSE |
| TERMINAL TYPE AND QUANTITY | 3 QUICK DISCONNECT, MALE AND 3 TAB, SOLDER LUG |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 360.000 NOMINAL AT 200 PCT ALL LOCATIONS |
| TRIP RELEASE AMBIENT TEMP RATING | 40.0 CELSIUS NOMINAL ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 140.0 ALL LOCATIONS |