| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUTMAGNETIC BLOWOUT |
| AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
| BODY LENGTH | 2.500 INCHES NOMINAL2.500 INCHES NOMINAL |
| BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPEMULTIPOLE-MULTIPLE ACTUATOR TYPE |
| BODY WIDTH | 1.940 INCHES NOMINAL1.940 INCHES NOMINAL |
| BOSS HEIGHT | 0.150 INCHES NOMINAL0.150 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 2.060 INCHES NOMINAL2.060 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 2.060 INCHES NOMINAL2.060 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL0.750 INCHES NOMINAL |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.060 INCHES NOMINAL2.060 INCHES NOMINAL |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
| FRAGILITY FACTOR | MODERATELY RUGGEDMODERATELY RUGGED |
| FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 2.0 AMPERES AC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 500.0 AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE(S)6 THREADED HOLE(S) |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.927 INCHES MAXIMUM2.927 INCHES MAXIMUM |
| NOMINAL THREAD SIZE | 0.138 INCHES |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 408.0 AC ALL LOCATIONS |
| POLE QUANTITY | 33 |
| RESET METHOD | MANUAL |
| SPECIAL HANDLING FEATURE | MAGNETICMAGNETIC |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSEGENERAL PURPOSE WAREHOUSE |
| SWITCH TERMINAL TYPE | WIRE LEAD |
| SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 125.0 AC AND 50.0 DC |
| SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROWSINGLE POLE, DOUBLE THROW |
| SWITCH CURRENT RATING AND TYPE IN AMPS | 5.0 AC AND 1.0 DC |
| SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE |
| TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
| TEST DATA DOCUMENT | 18876-10670787 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). |
| THREAD QUANTITY PER INCH | 3232 |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 20.000 MINIMUM AT 200 PCT AND 80.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
| UNPACKAGED UNIT WEIGHT | 0.600 POUNDS NOMINAL |