| POLE QUANTITY | 3 |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 1.4 AMPERES AC ALL LOCATIONS |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 480.0 AC ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| RESET METHOD | MANUAL |
| BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE |
| CASE MATERIAL | PLASTIC |
| TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1200.0 AC ALL LOCATIONS |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 40.000 MINIMUM AT 200 PCT AND |
| 100.000 MAXIMUM AT 200 PCT AND |
| 10.000 MINIMUM AT 300 PCT AND |
| 30.000 MAXIMUM AT 105 PCT AND |
| 6.000 MINIMUM AT 400 PCT AND |
| 18.000 MAXIMUM AT 400 PCT ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| ULTIMATE TRIP TIME PER POLE IN SECONDS | 150.000 MINIMUM AND |
| 500.000 MAXIMUM ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| BODY LENGTH | 3.719 INCHES NOMINAL |
| BODY WIDTH | 3.052 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 2.939 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.031 INCHES NOMINAL |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.750 INCHES NOMINAL |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.031 INCHES NOMINAL |
| BOSS HEIGHT | 0.156 INCHES NOMINAL |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.239 INCHES NOMINAL |
| THREAD SERIES DESIGNATOR | UNC |
| NOMINAL THREAD SIZE | 0.138 INCHES |
| THREAD QUANTITY PER INCH | 32 |
| MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND |
| MOISTURE RESISTANT |
| SPEC/STD CONTROLLING DATA | |
| MANUFACTURERS CODE | 10001 |
| MFR SOURCE CONTROLLING REFERENCE | 2843590 |