| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.050 INCHES MINIMUM AND 2.070 INCHES MAXIMUM |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.735 INCHES MINIMUM AND 0.765 INCHES MAXIMUM |
| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| BODY LENGTH | 2.480 INCHES MINIMUM AND 2.500 INCHES MAXIMUM |
| BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| BODY WIDTH | 2.265 INCHES MAXIMUM |
| BOSS HEIGHT | 0.150 INCHES NOMINAL |
| CASE MATERIAL | PLASTIC |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.940 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.735 INCHES MINIMUM AND 0.765 INCHES MAXIMUM |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | CORROSION RESISTANT AND MOISTURE RESISTANT AND SHOCKPROOF AND VIBRATIONPROOF AND FUNGUS RESISTANT |
| NOMINAL THREAD SIZE | 0.138 INCHES |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.625 INCHES MAXIMUM |
| RESET METHOD | MANUAL |
| POLE QUANTITY | 3 |
| THREAD QUANTITY PER INCH | 32 |
| THREAD SERIES DESIGNATOR | UNC |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.000 MINIMUM AT 200 PCT AND 22.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| UNPACKAGED UNIT WEIGHT | 11.100 OUNCES NOMINAL |
| SPECIAL HANDLING FEATURE | MAGNETIC |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |