5925-00-405-8061 CIRCUIT BREAKER Index 5950-00-405-8063 COIL,ELECTRICAL

National Stock Number:
5925-00-405-8062

Federal Supply Class:
5925

National Item Identification Number:
004058062

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
NEF42310021810CHALLENGER ELECTRICAL EQUIPMENT CORP


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
BODY HEIGHT3.406 INCHES NOMINAL
BODY LENGTH6.032 INCHES NOMINAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH2.750 INCHES NOMINAL
BOSS HEIGHT0.250 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH1.375 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE100.0 AMPERES AC AND 70.0 AMPERES DC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS15000.0 AC AND 10000.0 DC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY2 UNTHREADED HOLE(S)
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS480.0 AC AND 250.0 DC ALL LOCATIONS
POLE QUANTITY2
RESET METHODMANUAL
UNTHREADED MOUNTING HOLE DIAMETER0.225 INCHES NOMINAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY4 COMPRESSION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT24.000 MINIMUM AT 200 PCT AND 65.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING40.0 CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND TIME DELAY ALL LOCATIONS
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS


Click here to Register for Free 30-day Trial