POLE QUANTITY | 3 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 15.0 AMPERES AC ALL LOCATIONS |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC ALL LOCATIONS |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND |
| TIME DELAY ALL LOCATIONS |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 420.000 MINIMUM AT 200 PCT AND |
| 1500.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 175.0 ALL LOCATIONS |
BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
OVERALL LENGTH | 4.594 INCHES NOMINAL |
OVERALL HEIGHT | 3.531 INCHES NOMINAL |
OVERALL WIDTH | 3.844 INCHES NOMINAL |
MOUNTING FACILITY TYPE AND QUANTITY | 6 TERMINAL |
TERMINAL TYPE AND QUANTITY | 6 SCREW |
FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | 700.0 TO 1100.0 AC ALL LOCATIONS |
THE MANUFACTURERS DATA | |
MANUFACTURERS CODE | 30086 |
DESIGN CONTROL REFERENCE | ETN4322 |