| ACTUATOR FUNCTION | TRIP-RESETTRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE ONEAT POLE ONE |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUTMAGNETIC BLOWOUT |
| BODY LENGTH | 2.490 INCHES MINIMUM AND 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM2.510 INCHES MAXIMUM |
| BODY STYLE | SINGLE POLE TYPESINGLE POLE TYPE |
| BODY WIDTH | 0.740 INCHES MINIMUM AND 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM0.760 INCHES MAXIMUM |
| BOSS HEIGHT | 0.130 INCHES MINIMUM AND 0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM0.150 INCHES MAXIMUM |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.928 INCHES MINIMUM AND 1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM1.948 INCHES MAXIMUM |
| CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATIONOVERCURRENT SINGLE LOCATION |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.052 INCHES MINIMUM AND 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM2.072 INCHES MAXIMUM |
| FRAGILITY FACTOR | MODERATELY RUGGEDMODERATELY RUGGED |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANTFUNGUS RESISTANT |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATIONSERIES TRIP SINGLE LOCATION |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREETRIP FREE |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 50.0 DC SINGLE LOCATION50.0 DC SINGLE LOCATION |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE1 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 DC SINGLE LOCATION2000.0 DC SINGLE LOCATION |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 15.0 AMPERES DC SINGLE LOCATION15.0 AMPERES DC SINGLE LOCATION |
| MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE(S)2 THREADED HOLE(S) |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.461 INCHES MINIMUM AND 2.461 INCHES MINIMUM AND 2.481 INCHES MAXIMUM2.481 INCHES MAXIMUM |
| NOMINAL THREAD SIZE | 0.138 INCHES0.138 INCHES |
| POLE QUANTITY | 11 |
| RESET METHOD | MANUALMANUAL |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATIONTIME DELAY SINGLE LOCATION |
| TRIP RELEASE METHOD | MAGNETIC SINGLE LOCATIONMAGNETIC SINGLE LOCATION |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.800 MINIMUM AT 125 PCT AND 0.800 MINIMUM AT 125 PCT AND 3.000 MAXIMUM AT 125 PCT AND 3.000 MAXIMUM AT 125 PCT AND 0.180 MINIMUM AT 200 PCT AND 0.180 MINIMUM AT 200 PCT AND 0.550 MAXIMUM AT 200 PCT AND 0.550 MAXIMUM AT 200 PCT AND 0.070 MINIMUM AT 300 PCT AND 0.070 MINIMUM AT 300 PCT AND 0.220 MAXIMUM AT 300 PCT SINGLE LOCATION0.220 MAXIMUM AT 300 PCT SINGLE LOCATION |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION125.0 SINGLE LOCATION |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSEGENERAL PURPOSE WAREHOUSE |
| TERMINAL TYPE AND QUANTITY | 2 THREADED STUD2 THREADED STUD |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC)UNIFIED NATIONAL COARSE (UNC) |
| THREAD QUANTITY PER INCH | 3232 |