| ACTUATOR FUNCTION | TRIP-RESETTRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLEAT EACH POLE |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUTMAGNETIC BLOWOUT |
| AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 CONTROL1 CONTROL |
| BODY LENGTH | 2.490 INCHES NOMINAL2.490 INCHES NOMINAL |
| BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPEMULTIPOLE-MULTIPLE ACTUATOR TYPE |
| BODY WIDTH | 1.530 INCHES MAXIMUM1.530 INCHES MAXIMUM |
| BOSS HEIGHT | 0.150 INCHES NOMINAL0.150 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.940 INCHES NOMINAL1.940 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL0.750 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONSOVERCURRENT ALL LOCATIONS |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.060 INCHES NOMINAL2.060 INCHES NOMINAL |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL0.750 INCHES NOMINAL |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKEDONE AND TWO LINKED |
| FRAGILITY FACTOR | MODERATELY RUGGEDMODERATELY RUGGED |
| FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS400.0 ALL LOCATIONS |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONSSERIES TRIP ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREETRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE2 TOGGLE |
| MATERIAL | PLASTIC CASEPLASTIC CASE |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 AC ALL LOCATIONS2000.0 AC ALL LOCATIONS |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES AC ALL LOCATIONS5.0 AMPERES AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE(S)4 THREADED HOLE(S) |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.475 INCHES NOMINAL2.475 INCHES NOMINAL |
| NOMINAL THREAD SIZE | 3.5 MILLIMETERS3.5 MILLIMETERS |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS250.0 AC ALL LOCATIONS |
| POLE QUANTITY | 22 |
| RESET METHOD | MANUALMANUAL |
| SPECIAL HANDLING FEATURE | MAGNETICMAGNETIC |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSEGENERAL PURPOSE WAREHOUSE |
| SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC250.0 AC |
| SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROWSINGLE POLE, DOUBLE THROW |
| SWITCH CURRENT RATING AND TYPE IN AMPS | 10.0 AC10.0 AC |
| SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONEINTERNAL AT POLE ONE |
| SWITCH TERMINAL TYPE | TURRETTURRET |
| TERMINAL TYPE AND QUANTITY | 4 THREADED STUD4 THREADED STUD |
| THREAD SERIES DESIGNATOR | ISO SISO S |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 6.000 MINIMUM AT 150 PCT AND 6.000 MINIMUM AT 150 PCT AND 60.000 MAXIMUM AT 150 PCT AND 60.000 MAXIMUM AT 150 PCT AND 0.400 MINIMUM AT 400 PCT AND 0.400 MINIMUM AT 400 PCT AND 1.500 MAXIMUM AT 400 PCT ALL LOCATIONS1.500 MAXIMUM AT 400 PCT ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONSTIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONSMAGNETIC-HYDRAULIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS150.0 ALL LOCATIONS |
| ULTIMATE TRIP TIME PER POLE IN SECONDS | 6.000 MINIMUM AND 6.000 MINIMUM AND 60.000 MAXIMUM ALL LOCATIONS60.000 MAXIMUM ALL LOCATIONS |
| UNPACKAGED UNIT WEIGHT | 7.400 OUNCES NOMINAL7.400 OUNCES NOMINAL |