| ACTUATOR FUNCTION | TRIP-RESETTRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE ONEAT POLE ONE |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUTMAGNETIC BLOWOUT |
| BODY LENGTH | 2.480 INCHES MINIMUM AND 2.480 INCHES MINIMUM AND 2.500 INCHES MAXIMUM2.500 INCHES MAXIMUM |
| BODY STYLE | SINGLE POLE TYPESINGLE POLE TYPE |
| BODY WIDTH | 0.750 INCHES MAXIMUM0.750 INCHES MAXIMUM |
| BOSS HEIGHT | 0.150 INCHES NOMINAL0.150 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.940 INCHES NOMINAL1.940 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATIONOVERCURRENT SINGLE LOCATION |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.050 INCHES MINIMUM AND 2.050 INCHES MINIMUM AND 2.070 INCHES MAXIMUM2.070 INCHES MAXIMUM |
| FRAGILITY FACTOR | MODERATELY RUGGEDMODERATELY RUGGED |
| FREQUENCY IN HERTZ | 400.0 SINGLE LOCATION400.0 SINGLE LOCATION |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | MOISTURE RESISTANT AND MOISTURE RESISTANT AND SHOCK RESISTANT AND SHOCK RESISTANT AND VIBRATION RESISTANTVIBRATION RESISTANT |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATIONSERIES TRIP SINGLE LOCATION |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREETRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE1 TOGGLE |
| MATERIAL | PLASTIC CASEPLASTIC CASE |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SINGLE LOCATION1000.0 AC SINGLE LOCATION |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 15.0 AMPERES AC SINGLE LOCATION15.0 AMPERES AC SINGLE LOCATION |
| MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE(S)2 THREADED HOLE(S) |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.475 INCHES NOMINAL2.475 INCHES NOMINAL |
| NOMINAL THREAD SIZE | 0.138 INCHES0.138 INCHES |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC SINGLE LOCATION240.0 AC SINGLE LOCATION |
| POLE QUANTITY | 11 |
| RESET METHOD | MANUALMANUAL |
| SPECIAL HANDLING FEATURE | MAGNETICMAGNETIC |
| SPECIFICATION/STANDARD DATA | 81349-MIL-C-55629/1 GOVERNMENT SPECIFICATION81349-MIL-C-55629/1 GOVERNMENT SPECIFICATION |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSEGENERAL PURPOSE WAREHOUSE |
| TERMINAL TYPE AND QUANTITY | 2 THREADED STUD2 THREADED STUD |
| TEST DATA DOCUMENT | 81349-MIL-C-55629 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.).81349-MIL-C-55629 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). |
| THREAD QUANTITY PER INCH | 3232 |
| THREAD PITCH DIAMETERS | +0.1177 TO 0.1214 INCHES+0.1177 TO 0.1214 INCHES |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC)UNIFIED NATIONAL COARSE (UNC) |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 9.500 MINIMUM AT 200 PCT AND 9.500 MINIMUM AT 200 PCT AND 150.000 MAXIMUM AT 200 PCT SINGLE LOCATION150.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATIONTIME DELAY SINGLE LOCATION |
| TRIP RELEASE METHOD | MAGNETIC SINGLE LOCATIONMAGNETIC SINGLE LOCATION |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 SINGLE LOCATION115.0 SINGLE LOCATION |