5365-00-262-5858 SHIM Index 5961-00-262-5861 SEMICONDUCTOR DEVICE,DIODE

National Stock Number:
5925-00-262-5859

Federal Supply Class:
5925

National Item Identification Number:
002625859

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
APL111-1-43-30381541SENSATA TECHNOLOGIES MARYLAND, INC
APL111-55629-5-11981541SENSATA TECHNOLOGIES MARYLAND, INC
M55629/5-11981349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
MIL-C-55629/581349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
MIL-PRF-55629/581349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESETTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLEAT EACH POLE
ARC QUENCHING METHODMAGNETIC BLOWOUTMAGNETIC BLOWOUT
BODY LENGTH2.510 INCHES MAXIMUM2.510 INCHES MAXIMUM
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPEMULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH2.156 INCHES MINIMUM AND 2.156 INCHES MINIMUM AND 2.344 INCHES MAXIMUM2.344 INCHES MAXIMUM
BOSS HEIGHT0.109 INCHES MINIMUM AND 0.109 INCHES MINIMUM AND 0.171 INCHES MAXIMUM0.171 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.660 INCHES MINIMUM AND 1.660 INCHES MINIMUM AND 1.960 INCHES MAXIMUM1.960 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.719 INCHES MINIMUM AND 0.719 INCHES MINIMUM AND 0.781 INCHES MAXIMUM0.781 INCHES MAXIMUM
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONSOVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.046 INCHES MINIMUM AND 2.046 INCHES MINIMUM AND 2.078 INCHES MAXIMUM2.078 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.719 INCHES MINIMUM AND 0.719 INCHES MINIMUM AND 0.781 INCHES MAXIMUM0.781 INCHES MAXIMUM
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKEDONE, TWO, AND THREE LINKED
FRAGILITY FACTORMODERATELY RUGGEDMODERATELY RUGGED
FREQUENCY IN HERTZ400.0 ALL LOCATIONS400.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND FUNGUS RESISTANT AND MOISTURE RESISTANTMOISTURE RESISTANT
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONSSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY3 TOGGLE3 TOGGLE
MATERIALPLASTIC CASEPLASTIC CASE
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC ALL LOCATIONS1000.0 AC ALL LOCATIONS
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE30.0 AMPERES AC ALL LOCATIONS30.0 AMPERES AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY6 THREADED HOLE(S)6 THREADED HOLE(S)
MOUNTING SURFACE TO TERMINAL END DISTANCE2.553 INCHES MAXIMUM2.553 INCHES MAXIMUM
NOMINAL THREAD SIZE0.138 INCHES0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC ALL LOCATIONS240.0 AC ALL LOCATIONS
POLE QUANTITY33
RESET METHODMANUALMANUAL
SPECIFICATION/STANDARD DATA81349-MIL-C-55629/5 GOVERNMENT SPECIFICATION81349-MIL-C-55629/5 GOVERNMENT SPECIFICATION
STORAGE TYPEGENERAL PURPOSE WAREHOUSEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY6 THREADED STUD6 THREADED STUD
TEST DATA DOCUMENT81349-MIL-C-55629 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.).81349-MIL-C-55629 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.).
THREAD QUANTITY PER INCH3232
THREAD PITCH DIAMETERS+0.1177 TO 0.1214 INCHES+0.1177 TO 0.1214 INCHES
THREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)UNIFIED NATIONAL COARSE (UNC)
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT9.500 MINIMUM AT 200 PCT AND 9.500 MINIMUM AT 200 PCT AND 150.000 MAXIMUM AT 200 PCT ALL LOCATIONS150.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONSTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC ALL LOCATIONSMAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT115.0 ALL LOCATIONS115.0 ALL LOCATIONS


Click here to Register for Free 30-day Trial