| ACTUATOR FUNCTION | RESET |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.060 INCHES NOMINAL |
| FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 125.0 AC SINGLE LOCATION |
| OVERALL HEIGHT | 2.530 INCHES NOMINAL |
| OVERALL LENGTH | 3.330 INCHES NOMINAL |
| OVERALL WIDTH | 0.760 INCHES NOMINAL |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 AC SINGLE LOCATION |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 2.0 AMPERES AC SINGLE LOCATION |
| MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE(S) |
| NOMINAL THREAD SIZE | 0.138 INCHES |
| POLE QUANTITY | 1 |
| RESET METHOD | MANUAL |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
| TRIP RELEASE METHOD | MAGNETIC SINGLE LOCATION |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 1.020 MINIMUM AT 125 PCT AND 6.000 MAXIMUM AT 125 PCT AND 0.250 MINIMUM AT 200 PCT AND 0.850 MAXIMUM AT 200 PCT AND 0.090 MINIMUM AT 300 PCT AND 3.000 MAXIMUM AT 300 PCT SINGLE LOCATION |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
| TERMINAL TYPE AND QUANTITY | 2 THREADED STUD |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| THREAD QUANTITY PER INCH | 32 |