5905-00-247-2996 RESISTOR,FIXED,FILM Index 5895-00-247-3004 CONTROL,RECEIVER

National Stock Number:
5925-00-247-3001

Federal Supply Class:
5925

National Item Identification Number:
002473001

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
2XAM1516MG3-15-250-2-5074193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESETTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLEAT EACH POLE
BODY LENGTH3.719 INCHES NOMINAL3.719 INCHES NOMINAL
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPEMULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH2.031 INCHES NOMINAL2.031 INCHES NOMINAL
BOSS HEIGHT0.156 INCHES NOMINAL0.156 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH3.063 INCHES NOMINAL3.063 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH1.031 INCHES NOMINAL1.031 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONSOVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH1.031 INCHES NOMINAL1.031 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.750 INCHES NOMINAL2.750 INCHES NOMINAL
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE AND TWO LINKEDONE AND TWO LINKED
FREQUENCY IN HERTZ50.0 ALL LOCATIONS50.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND FUNGUS RESISTANT AND MOISTURE RESISTANTMOISTURE RESISTANT
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONSSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC ALL LOCATIONS250.0 AC ALL LOCATIONS
MANUAL ACTUATOR TYPE AND QUANTITY2 TOGGLE2 TOGGLE
MATERIALPLASTIC CASEPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE15.0 AMPERES AC ALL LOCATIONS15.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1500.0 AC ALL LOCATIONS1500.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 THREADED HOLE(S)4 THREADED HOLE(S)
MOUNTING SURFACE TO TERMINAL END DISTANCE3.427 INCHES NOMINAL3.427 INCHES NOMINAL
NOMINAL THREAD SIZE0.138 INCHES0.138 INCHES
POLE QUANTITY22
RESET METHODMANUALMANUAL
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT13.000 MINIMUM AT 150 PCT AND 13.000 MINIMUM AT 150 PCT AND 40.000 MAXIMUM AT 150 PCT AND 40.000 MAXIMUM AT 150 PCT AND 1.000 MINIMUM AT 400 PCT AND 1.000 MINIMUM AT 400 PCT AND 3.000 MAXIMUM AT 400 PCT ALL LOCATIONS3.000 MAXIMUM AT 400 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONSTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONSMAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS125.0 ALL LOCATIONS
ULTIMATE TRIP TIME PER POLE IN SECONDS10.000 MINIMUM AND 10.000 MINIMUM AND 80.000 MAXIMUM ALL LOCATIONS80.000 MAXIMUM ALL LOCATIONS
TERMINAL TYPE AND QUANTITY4 THREADED STUD4 THREADED STUD
THREAD QUANTITY PER INCH3232
THREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)UNIFIED NATIONAL COARSE (UNC)