| ACTUATOR FUNCTION | TRIP-RESETTRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLEAT EACH POLE |
| ARC QUENCHING METHOD | AIRAIR |
| AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM1 ALARM |
| BODY LENGTH | 2.500 INCHES NOMINAL2.500 INCHES NOMINAL |
| BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPEMULTIPOLE-MULTIPLE ACTUATOR TYPE |
| BODY WIDTH | 2.250 INCHES NOMINAL2.250 INCHES NOMINAL |
| BOSS HEIGHT | 0.140 INCHES NOMINAL0.140 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.938 INCHES NOMINAL1.938 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL0.750 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONSOVERCURRENT ALL LOCATIONS |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL0.750 INCHES NOMINAL |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.062 INCHES NOMINAL2.062 INCHES NOMINAL |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKEDONE, TWO, AND THREE LINKED |
| FRAGILITY FACTOR | MODERATELY RUGGEDMODERATELY RUGGED |
| FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS400.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | MOISTURE RESISTANT AND MOISTURE RESISTANT AND FUNGUS RESISTANTFUNGUS RESISTANT |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONSSERIES TRIP ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREETRIP FREE |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS250.0 AC ALL LOCATIONS |
| MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE3 TOGGLE |
| MATERIAL | PLASTIC CASEPLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 25.0 AMPERES AC ALL LOCATIONS25.0 AMPERES AC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS1000.0 AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE(S)6 THREADED HOLE(S) |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.611 INCHES NOMINAL2.611 INCHES NOMINAL |
| NOMINAL THREAD SIZE | 0.138 INCHES0.138 INCHES |
| POLE QUANTITY | 33 |
| RESET METHOD | MANUALMANUAL |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 28.000 MINIMUM AT 200 PCT AND 28.000 MINIMUM AT 200 PCT AND 95.000 MAXIMUM AT 200 PCT ALL LOCATIONS95.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONSTIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONSMAGNETIC-HYDRAULIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS150.0 ALL LOCATIONS |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSEGENERAL PURPOSE WAREHOUSE |
| SWITCH LOCATION AND POSITION DESIGNATION | EXTERNAL AT POLE ONEEXTERNAL AT POLE ONE |
| SWITCH TERMINAL TYPE | TURRETTURRET |
| SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 125.0 AC AND 125.0 AC AND 50.0 DC50.0 DC |
| SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROWSINGLE POLE, DOUBLE THROW |
| SWITCH CURRENT RATING AND TYPE IN AMPS | 5.0 AC AND 5.0 AC AND 1.0 DC1.0 DC |
| TERMINAL TYPE AND QUANTITY | 6 THREADED STUD6 THREADED STUD |
| THREAD PITCH DIAMETERS | +0.1177 TO 0.1214 INCHES+0.1177 TO 0.1214 INCHES |
| THREAD QUANTITY PER INCH | 3232 |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC)UNIFIED NATIONAL COARSE (UNC) |