| ACTUATOR FUNCTION | TRIP W/SEPARATE RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
| CIRCUIT PROTECTION TYPE | OVERCURRENT SECOND LOCATION |
| CIRCUIT PROTECTION TYPE | OVERCURRENT FIRST LOCATION |
| CIRCUIT PROTECTION TYPE | UNDERVOLTAGE THIRD LOCATION |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| OVERALL LENGTH | 17.688 INCHES NOMINAL |
| OVERALL WIDTH | 8.250 INCHES NOMINAL |
| MATERIAL | PLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 125.0 AMPERES AC AND 125.0 AMPERES DC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC AND 10000.0 DC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE(S) |
| NOMINAL THREAD SIZE | 0.375 INCHES |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC AND 250.0 DC ALL LOCATIONS |
| OVERALL HEIGHT | 4.688 INCHES NOMINAL |
| POLE QUANTITY | 3 |
| RESET METHOD | MANUAL |
| TERMINAL TYPE AND QUANTITY | 6 SCREW |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| THREAD QUANTITY PER INCH | 16 |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 108.000 MINIMUM AT 200 PCT AND 500.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| TRIP RELEASE AMBIENT TEMP RATING | 25.0 CELSIUS NOMINAL ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | THERMAL ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |