| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| BODY HEIGHT | 2.257 INCHES MINIMUM AND 2.277 INCHES MAXIMUM |
| BODY LENGTH | 5.790 INCHES MINIMUM AND 5.810 INCHES MAXIMUM |
| BODY STYLE | SINGLE POLE TYPE |
| BODY WIDTH | 1.016 INCHES MINIMUM AND 1.036 INCHES MAXIMUM |
| BOSS HEIGHT | 0.209 INCHES MINIMUM AND 0.229 INCHES MAXIMUM |
| CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 75.0 AMPERES DC SINGLE LOCATION |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 DC SINGLE LOCATION |
| MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE(S) AND 1 UNTHREADED HOLE(S) AND 1 SLOT |
| MOUNTING SLOT WIDTH | 0.178 INCHES NOMINAL |
| NOMINAL THREAD SIZE | 0.138 INCHES |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 125.0 DC SINGLE LOCATION |
| POLE QUANTITY | 1 |
| RESET METHOD | MANUAL |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| TERMINAL TYPE AND QUANTITY | 2 SCREW |
| THREAD QUANTITY PER INCH | 32 |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.150 MINIMUM AT 200 PCT AND 0.700 MAXIMUM AT 200 PCT SINGLE LOCATION |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
| TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
| UNTHREADED MOUNTING HOLE DIAMETER | 0.164 INCHES NOMINAL |