| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
| BODY LENGTH | 4.750 INCHES NOMINAL |
| BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| BODY WIDTH | 2.072 INCHES MAXIMUM |
| BOSS HEIGHT | 0.219 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.026 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.547 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT FIRST LOCATION |
| CIRCUIT PROTECTION TYPE | OVERVOLTAGE SECOND LOCATION |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.750 INCHES NOMINAL |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.026 INCHES NOMINAL |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | VIBRATION RESISTANT AND SHOCK RESISTANT AND MOISTURE RESISTANT AND SALT SPRAY PROOF AND FUNGUS RESISTANT |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP FIRST LOCATION |
| INTERNAL TRIP RELEASE CONFIGURATION | RELAY TRIP SECOND LOCATION |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 125.0 DC FIRST LOCATION |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 30.0 DC SECOND LOCATION |
| MATERIAL | PLASTIC CASE |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 DC ALL LOCATIONS |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES DC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE(S) AND 4 SLOT |
| MOUNTING SLOT WIDTH | 0.164 INCHES NOMINAL |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.485 INCHES NOMINAL |
| NOMINAL THREAD SIZE | 0.138 INCHES |
| POLE QUANTITY | 2 |
| RESET METHOD | MANUAL |
| SPECIAL HANDLING FEATURE | MAGNETIC |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 30.000 MINIMUM AT 200 PCT AND 100.000 MAXIMUM AT 200 PCT FIRST LOCATION |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS SECOND LOCATION |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY FIRST LOCATION |
| TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 FIRST LOCATION |
| UNPACKAGED UNIT WEIGHT | 1.300 POUNDS NOMINAL |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
| SWITCH CURRENT RATING AND TYPE IN AMPS | 5.0 AC |
| SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE |
| SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
| SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 125.0 AC |
| TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
| TEST DATA DOCUMENT | 80063-SM-A-742924 DRAWING (THIS IS THE BASIC GOVERNING DRAWING, SUCH AS A CONTRACTOR DRAWING, ORIGINAL EQUIPMENT MANUFACTURER DRAWING, ETC.; EXCLUDES ANY SPECIFICATION, STANDARD OR OTHER DOCUMENT THAT MAY BE REFERENCED IN A BASIC GOVERNING DRAWING) |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| THREAD QUANTITY PER INCH | 32 |