5305-00-144-0433 SCREW,CAP,SOCKET HEAD Index 5925-00-144-0438 CIRCUIT BREAKER

National Stock Number:
5925-00-144-0434

Federal Supply Class:
5925

National Item Identification Number:
001440434

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
BAR181-210018AVAHO ACQUISITION CORP DBA IMPAC
NAF1131-1099993DEPARTMENT OF THE NAVY
SM-B-112884-180063US ARMY COMMUNICATIONS & ELECTRONICS MATERIEL READINESS COMMAND LOGISTICS ENGINEERING DIR
PM1082647SENSATA TECHNOLOGIES, INC.


Techincal Specification:
ACTUATOR FUNCTIONRESETRESET
ACTUATOR POSITION DESIGNATIONAT POLE ONEAT POLE ONE
ARC QUENCHING METHODAIRAIR
BODY STYLESINGLE POLE TYPESINGLE POLE TYPE
BODY WIDTH1.188 INCHES NOMINAL1.188 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.156 INCHES NOMINAL1.156 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATIONOVERCURRENT SINGLE LOCATION
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH1.563 INCHES NOMINAL1.563 INCHES NOMINAL
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOFDUSTPROOF
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATIONSERIES TRIP SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 PUSH BUTTON1 PUSH BUTTON
OVERALL LENGTH2.000 INCHES NOMINAL2.000 INCHES NOMINAL
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE10.0 AMPERES DC SINGLE LOCATION10.0 AMPERES DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS600.0 DC SINGLE LOCATION600.0 DC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY2 UNTHREADED HOLE(S)2 UNTHREADED HOLE(S)
MOUNTING SURFACE TO TERMINAL END DISTANCE1.266 INCHES NOMINAL1.266 INCHES NOMINAL
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS30.0 DC SINGLE LOCATION30.0 DC SINGLE LOCATION
POLE QUANTITY11
RESET METHODMANUALMANUAL
UNTHREADED MOUNTING HOLE DIAMETER0.188 INCHES NOMINAL0.188 INCHES NOMINAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY2 SCREW2 SCREW
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT30.000 NOMINAL AT 200 PCT SINGLE LOCATION30.000 NOMINAL AT 200 PCT SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATIONTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODMAGNETIC SINGLE LOCATIONMAGNETIC SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 SINGLE LOCATION125.0 SINGLE LOCATION


Click here to Register for Free 30-day Trial