6650-00-140-2353 EYEPIECE ASSEMBLY,OPTICAL INSTRU Index 5925-00-140-2355 CIRCUIT BREAKER

National Stock Number:
5925-00-140-2354

Federal Supply Class:
5925

National Item Identification Number:
001402354

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
SMA742925-180063US ARMY COMMUNICATIONS & ELECTRONICS MATERIEL READINESS COMMAND LOGISTICS ENGINEERING DIR


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESETTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLEAT EACH POLE
ARC QUENCHING METHODAIRAIR
BODY LENGTH2.500 INCHES NOMINAL2.500 INCHES NOMINAL
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPEMULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH1.500 INCHES NOMINAL1.500 INCHES NOMINAL
BOSS HEIGHT0.150 INCHES NOMINAL0.150 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.928 INCHES NOMINAL1.928 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.750 INCHES NOMINAL0.750 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONSOVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.750 INCHES NOMINAL0.750 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.062 INCHES NOMINAL2.062 INCHES NOMINAL
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE AND TWO LINKEDONE AND TWO LINKED
FRAGILITY FACTORMODERATELY RUGGEDMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 ALL LOCATIONS60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND FUNGUS RESISTANT AND MOISTURE RESISTANTMOISTURE RESISTANT
INTERNAL TRIP RELEASE CONFIGURATIONRELAY TRIP SECOND LOCATIONRELAY TRIP SECOND LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP FIRST LOCATIONSERIES TRIP FIRST LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY2 TOGGLE2 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC ALL LOCATIONS1000.0 AC ALL LOCATIONS
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE15.0 AMPERES AC ALL LOCATIONS15.0 AMPERES AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 THREADED HOLE(S)4 THREADED HOLE(S)
MOUNTING SURFACE TO TERMINAL END DISTANCE2.692 INCHES NOMINAL2.692 INCHES NOMINAL
NOMINAL THREAD SIZE0.138 INCHES0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS125.0 AC ALL LOCATIONS125.0 AC ALL LOCATIONS
POLE QUANTITY22
RESET METHODMANUALMANUAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY6 THREADED STUD6 THREADED STUD
THREAD QUANTITY PER INCH3232
THREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)UNIFIED NATIONAL COARSE (UNC)
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT2.000 MINIMUM AT 200 PCT AND 2.000 MINIMUM AT 200 PCT AND 12.000 MAXIMUM AT 200 PCT FIRST LOCATION12.000 MAXIMUM AT 200 PCT FIRST LOCATION
TRIP RELEASE CHARACTERISTICINSTANTANEOUS SECOND LOCATIONINSTANTANEOUS SECOND LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY FIRST LOCATIONTIME DELAY FIRST LOCATION
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONSMAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS125.0 ALL LOCATIONS