| POLE QUANTITY | 2 |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 100.0 AMPERES AC AND |
| 10000.0 AMPERES DC ALL LOCATIONS |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| TERMINAL TYPE AND QUANTITY | 4 COMPRESSION |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC AND |
| 250.0 DC ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND |
| TIME DELAY ALL LOCATIONS |
| RESET METHOD | MANUAL |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
| CASE MATERIAL | PLASTIC |
| TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 15000.0 AC AND |
| 15000.0 DC ALL LOCATIONS |
| TRIP RELEASE AMBIENT TEMP RATING | 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 300.000 MINIMUM AT 150 PCT AND |
| 1400.000 MAXIMUM AT 150 PCT AND |
| 100.000 MINIMUM AT 200 PCT AND |
| 400.000 MAXIMUM AT 200 PCT AND |
| 30.000 MINIMUM AT 300 PCT AND |
| 100.000 MAXIMUM AT 300 PCT AND |
| 16.000 MINIMUM AT 400 PCT AND |
| 55.000 MAXIMUM AT 400 PCT AND |
| 10.000 MINIMUM AT 500 PCT AND |
| 35.000 MAXIMUM AT 500 PCT AND |
| 0.040 MINIMUM AT 1000 PCT AND |
| 10.000 MAXIMUM AT 1000 PCT ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 117.0 ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| OVERALL LENGTH | 10.180 INCHES NOMINAL |
| OVERALL HEIGHT | 8.250 INCHES NOMINAL |
| OVERALL WIDTH | 5.500 INCHES NOMINAL |
| NOMINAL THREAD SIZE | 0.312 INCHES |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| ACTUATOR FUNCTION | TRIP W/SEPARATE RESET |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
| FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
| ARC QUENCHING METHOD | DEION |
| PRECIOUS MATERIAL | SILVER |
| SPECIAL FEATURES | MTG HOLES ON 7.250 IN. BY 2.750 IN. MTG CENTERS |