| EFFECTIVE HEAT TRANSFER SURFACE AREA | 7.0 SQUARE FEET |
| CAPACITY RATING | 550.0 GALLONS PER HOUR |
| CONNECTION TYPE | THREADED EXTERNAL PIPE CONDENSATE RETURN |
| CONNECTION TYPE | THREADED EXTERNAL PIPE STEAM INLET |
| CONNECTION TYPE | THREADED EXTERNAL PIPE HEATING FLUID INLET |
| CONNECTION TYPE | THREADED EXTERNAL PIPE HEATING FLUID OUTLET |
| DIAMETER | 6.625 INCHES MAXIMUM |
| HEAT TRANSFER METHOD | INDIRECT |
| LENGTH | 40.000 INCHES MAXIMUM |
| MATERIAL | COPPER OR COPPER ALLOY TUBES |
| MATERIAL | STEEL OR IRON CAST TUBE SHEET |
| MATERIAL | STEEL SHELL |
| MAXIMUM STEAM WORKING PRESSURE | 125.0 POUNDS PER SQUARE INCH |
| NONDEFINITIVE SPEC/STD DATA | 2 TYPE AND A DESIGN AND 2 CLASS AND A STYLE |
| STYLE DESIGNATOR | STRAIGHT PLAIN TUBE CYLINDRICAL |
| TUBE QUANTITY | 12 |
| TUBING OUTSIDE DIAMETER | 0.750 INCHES NOMINAL BOTH INLET AND OUTLET TUBE ENDS |
| TUBE ATTACHMENT METHOD | SEAL-WELDED BOTH ENDS |